Wyoming Digital Archives

 
First Page
 Definitions of Terms Relating 

to Plastics (ASTM Designation: D -883-T), and abbreviations are in accordance 

with Abbreviations of Terms Relating to Plastics (ASTM Designation: D -1600- 

61-T), unless otherwise indicated. The abbreviation for polyethylene plastics 

is PE. 

3.2 Plastic Pipe and Terminology. 

3.2.1 Pipefer,inulo_iy - The pipe terminology (Inc. Imulas are in accordance with 

1 those " . ed in lentative SpeciFication for P, i ./,_thylone (PI:) Plastic Pipe 

(i��:;ll" 1 Designation: 0 -;'239 -G4 -T) and are as follows: 0. 

'. Standard 1'hermo,lastic PiLc Dir;etision Ratio SDR 

___. 

The stanrtard thermoplastic pipe dimension ratio SDR) of pipe with inside 

control diameters is the ratio of the pipe's inside diameter to its wall 

thickness in inches. The SDR values shall be expressed to the nearest 0.5. 

Hydrostatic Design Stress 

lie estimated Waximuin tensile stress in the walliof the pipe in the 

circunii`erential orientation due to internal hydrostatic water pressure that. 

can he applied continuously with a high degree of certainty that failure of 

the pipe will not occur. 

Pressure Rating (PR) 

The estimated maximum pressure that water i�� the pipe can exert continuously 

with a high degree of certainty that failure of the pipe will not occur. 

Related Between Standard Dimension Ratio, Hydrostatic Design Stress and 

PresSL,re Rating 

TTie i" ol owing expression, commonly known as the ISO equationi, is used in 

this specification to relate standard,dimension ratio, hydrostatic design 

stress, and pressure ratings of pipe with inside controlled diameters. 

2S = SUR 1 or 2S ID 1 

Where: + 

S Hydrostatic design stress, in pounds per quare inch 

P Pressure rating, in pounds per square inti 

ID Average inside diameter in inches 

t Minimum wall thickness in inches, and 

SDR Standard Thermoplastic pipe dimension ration, (IC/t for PE pipe) 

The pipe materials designation code shall consist of the abbreviation PE for 

the type of plastic, followed by the ASTM Type and Grade in Arabic numerals. 

and the hydrostatic design stress in units of 100 psi with any decimal figures 

dropped. Where the hydrostatic design stress code contains less than two 

figures, a cipher shall be used before the number. Thus a complete material 

code shall consist of two letters and four figures for PE plastic pipe materials. 

(See Section 3.2) 

3.3 The plumbing terminology used in this Standard is in accordance with the 

definitions given in the Uniform Plumbing Code,published by the International 

Association of Plumbing and iiechanical Official. 

4. SAMPLING AND GENERAL TEST CO`lDITIONS 

4.1 Sampling - A,sample of pipe and fittings sufficient to determine conformance 

with this Standard may be taken at random from each lot or shipment. About - 

60 feet of each size pipe is required.to make the prescribed tests. 

r Seems ISO R161-1960, Pipes of Plastics Materials for the Transport of Fluids (outside. "  

diameters and nominal pressures) Part 1, Metric Series. 

{'agu 3 

PS 24-69 

��4.2 Conditioning! test s��ecimens - The specimens shall be conditioned prior to 

test at 73A0 ! 3.6 F (23 1 20 C) and 50 1 5 percent relative humidity for 

not less than 48 hours in accordance with Procedure A in Standard Method of 

Conditioning Plastics and Electrical Insulation Materials for Testing (ASTM 

Designation: D418 -G1) for those tests where conditioning is required and 

in all cases of disagreement. 

4.3 

Test conditions - Tests shall be conducted in a laboratory atmosphere of 

73.40 " 1. 3,60 F (23 t 20 C) and 50 t 5 percent realtive humidity, unless 

otherwise specified in the test methods or in this specification. 

4.4 

The specific methods of test are listed below, following the property i 

requirements. 

5. 'PIPE MATERIAL REQUIREMENTS 

5.1 

For material- The polyethylene extrusion compound from which the pipe is 

manufactured shall meet the requirements of Type III .Grade 3, Class C 

material as described in ASTM D -1248-60-T, "Specification for Polyethylene 

Molding and Extrusion Compounds". It shall contain at least 2 percent of 

carbon black for weatherability protection. The compound shall have an 

hydrostatic design stress for water of 630 psi at 73.40 F and 500. psi at 

1000 F as recommended by the Plastics Pipe Institute, a Division of the 

Society of the Plastics Industry. Pipe, extruded from such compounds, are 

designated PE 3306. It shall be listed as an approved material by the 

National Sanitation Foundation for use with potable water. The flow rate 

by extrusion rheometer, as measured according to the procedure outlined i'n. 

ASTM Designation D -1238-62-T, "Measuring Flow Rates of Thernioplastics by 

Extrusion Plastometer", shall be not more than 0,25 gms/lOmiri. when deter- 

mined at a .test temperature of 3100 C and using a plunger load of 27,5 lbs, .' 

I 

5.2 

Rework material - Clean rework material generated from the manufacturer's 

own production may be used providing the product produced meets all the 

requirements of this specification. 

6, REQUIREMENTS OF PIPE 

6.1 

General - The pipe shall be homogenous throughout and free from visible 

cracks, holes, foreign inclusions or other injurious defects and shall be, as 

uniform in color, opacity, density and other physical properties as 

commercially practicable. 

6,2 

Flow rate by extrusion rheometer - A sample cut from the pipe shall have flow. 

rate of less than 0.5 gms/10 min. when measured according to the test method 

that follows: 

Test Method - The sample shall be prepared by cutting the pipe into uniform 

pellets approximately 1/8" by 1/8" by wall thickness. The flow rate shall 

be measured according to ASTM Designation D -1238-62-T. 

{1�� "Measuring Flow Rates of Thermopl$stics by Extrusion Plastometer.''. 

The test temperature shall be 310 C and the plunger load 27.5 lbs. 

6.4 

6.4.1 

Testing Pipe 

Minimum Burst Pressure 

Requirement - The minimum burst pressure at 73.40 F of pipe of 160 psi 

pressure rating shall be 630 psi. 

Test Method - The minimum burst pressure shall be determined.with at least 

5 specimens selected at random in accordance with Tentative Method of 

Short-term Rupture of Thermoplastic Pipe and Fittings (ASTM Designation 

D -1599-62-T). The time of testing each specimen shall be between 60'and 90 

seconds. The pressure medium shall be water. 

6.3 

Dili ." ions - Any length of" pipe may be used to drterminc dimensions. 

shall be made in accordance with Method of' c.,,:inrining " 

,t.. 

I)imr nus w "ihcrupplasl.ic Pipe (ASPM 0 :.,nation 

6.3.1 

Pipe 

t 

6.3.1.1 

Pipe Diameter 

Requirements - The inside diameter of the pipe shall meet the requirements 

given in Table I. 

Test Method - The inside diameter of the pipe shall be measured with a 

tapered plug gauge in accordance with Section 5 of ASTM Designation 

0-2122-62-T. 

y'. 

6.3.1.2 

Pipe hall Thickness 

Requirements - The wall thickness -of the pipe shall meet the requirements 

" 

given in Table I. 

Test !Method - Sufficient but not less than four wall thickness measurements 

shall be made in accordance with Section 4 of ASTM Designation D -2122-62-T" . 

to determine the maximum and minimum values. 

6.3.1.3 

Pipe Length - The pipe shall be in coils in lengtis 

as agreed upon between 

the purchaser and the seller. 

TABLE I 

DIMENSIONS AND TOLERANCES FOR PE WATER SERVICE PIPE . 

Inside Diameter 

Nominal 

To erance on Wall Thickness Pressure. 

Pipe Size SDR Average Ave_ rage Mi nimum Tolerance Ratin 

(Inch! nc (inch) (inch) 5I 

3/4 

7 0.87.4 0.010 - 0.015 0.116 0.020 160 

1 

7 1.049 0.010 - 0.020 0.150 0.020 160 

1 1/4 

7 1.380 0.010 - 0.020 0.197 0.024 160 

6.4 

6.4.1 

Testing Pipe 

Minimum Burst Pressure 

Requirement - The minimum burst pressure at 73.40 F of pipe of 160 psi 

pressure rating shall be 630 psi. 

Test Method - The minimum burst pressure shall be determined.with at least 

5 specimens selected at random in accordance with Tentative Method of 

Short-term Rupture of Thermoplastic Pipe and Fittings (ASTM Designation 

D -1599-62-T). The time of testing each specimen shall be between 60'and 90 

seconds. The pressure medium shall be water. 

Page 5 

PS 24-69 

6.4.2 Sustained Pro!...uro of Pilc - The pilin shall naL fail balloon burst or weep 

when tested at the condition given in Table 3 in accordance with the method 

that follows: 

Test Method - 'Ilia sustained pressure test shall be in accordance with Method 

of Testing for 'time -to -Failure of Plastic Pipe Under Long -Term Hydrostatic 

Pressure (ASTM Designation D -1598-63-T) except that the pressure and 

temperatures as specified in Table 3 shall be maintained for the times given 

in Table 3. Tile test specimens shall be selected at random. Eighteen 

specimens, each at least 10 times the nominal diameter in.length, but not 

less than 10 inches or more than 3 feet between end closures and containing 

the marking, shall be tested individually with water as the test medium. 

Six specimens shall be tested at each temperature. Failure of two of the 

six specimens tested at any temperature constitutes failure of the test. 

Failure of one of six specimens at any temperature is cause for retest of 

six additional specimens at that temperature. Failure of one of six specimens, 

tested in retest constitutes failure in the test. Failure of the pipe shall 

be as defined in ASTM Designation D -1598-63-T, Section 4, namely: 

Failure - Any continuous loss of pressure resulting from the transmission of 

the test liquid through the body of the specimen under test. 

Ballooning - Any abnormal localized expansion of a specimen while under test. 

Bursting   Failure by a break in the specimen with immediate loss of test 

liquid. 

Seepage or Weeping - Failure that occurs through essentially microscopic 

breaks in the specimen wall. 

TABLE 3 

SUSTAINED PRESSURE TEST REQUIREMENTS - PE PIPE 

Requirement - Rings cut from pipe shall elongate to the dimensions given 

in Table 4. 

Test Method - One-half inch rings shall be leanly cut from pipe. The ring 

specimens shall be placed over two 1/4 inch pins capable of being separated 

at a rate of 2 inches per minute. The rings shall not rupture.in less than 

the distance shown in Table 4. 

Test 

For 160 psi 

Temperature 

Pressure Rated 

Hours 

Sizes 

F 

Pipe 

Test Time 

All 

73.4 

325 

1,000 

All 

100 

265 

1,000 

All 

194 

110 " 

300 

6.4.3 

Ring Pull Test 

Requirement - Rings cut from pipe shall elongate to the dimensions given 

in Table 4. 

Test Method - One-half inch rings shall be leanly cut from pipe. The ring 

specimens shall be placed over two 1/4 inch pins capable of being separated 

at a rate of 2 inches per minute. The rings shall not rupture.in less than 

the distance shown in Table 4. 

TABLE 4 

ELONGATION REQUIREI4EIlT - PE PIPE 

`"  s:'`'' Pipe Size 3/4" 

Elongation 8 1/2" 

1"1 1/4" 

10" 12" 

P,. u 

I" "  4-G9 

7. QUALITY PRODUCTION CONTROL 

7.1 Manufacturers shall conduct daily tests (within their own plant facilities) 

on samples from every coil, once every hour or each operating shift, which- 

ever is less frequent, to insure that the pipe meets the requirements of 

this Standard. These tests must include 6,2, 6.3, 6.4.1 and 6.4.3. 

7.2 . Test records for the above tests shall be maintained for a period of not 

less than two years. 

B. MARKING 

8.1 Marking on pipe shall include the following spaced It intervals of not more 

than two feet: 

a Company name or registered trademark of the manufacturer 

b Nominal size and the word pipe 

c : PE 3306 JJ>r1W C464t 

d Pipe pressure rating (160 psi) 

a PS 24-69 

~'' f NSF.Seal of Approval 

g) Any other markings required 

h)) Code control identification 

Ratified by Membership: 1968 

.'Revised and. Ratified by Membership: 1969 

g 