  	1303.5.2 SOIL-GAS-RETARDER. The soil in crawl

   		brick veneer or other masonry ledge is installed, the   	spaces shall be covered with a continuous layer of

   		course immediately below that ledge shall be sealed.   	minimum  6-mil  (0.15mm)  polyethylene  soil-gas-

   		Joints,cracks or other openings around all penetrations   	retarder. The ground cover shall be lapped a minimum

   		of both exterior and interior surfaces of masonry block

      										50

    		of 12 inches (305 mm) at joints and shall extend to all   	1303.8 VENT PIPE ACCESSIBILITY.  Radon vent

   		foundation walls enclosing the crawl space area.   		pipes shall be accessible for future fan installation

      											through an attic or other area outside the habitable

    		1303.5.3  VENT  PIPE.  A  plumbing tee  or  other   	space.

   		approved connection shall be  inserted horizontally

   		beneath the sheeting and connected to a 3- or 4-inch       		EXCEPTION:  The radon vent pipe need

   		diameter (76 mm or 102mm) fitting with a vertical       		not be accessible in an attic space where an

   		vent pipe installed through the sheeting. The vent pipe       		approved  roof-top   electrical   supply   is

   		shall be extended up through the building  floors,       		provided for future use.

   		terminate at least 12 inches (305 mm) above the roof

   		in a location at least 10 feet(3048 nun)away from any   	1303.9   VENT   PIPE   IDENTIFICATION.   All

   		window or other opening into the conditioned spaces   	exposed and visible interior radon vent pipes shall be

   		of the building that is less than 2 feet(610 mm)below   	identified with at least one label on each floor and in

   		the exhaust point, and 10 feet (3048 mm) from any   	accessible  attics.    The  label  shall  read:  "Radon

   		window or other opening in adjoining or adjacent   	Reduction System".

   		buildings.

      											1303.10     COMBINATION     FOUNDATIONS.

   		1303.6      	PASSIVE      	SUB-SLAB   	Combination   basement/crawl   space   or   slab-on

   		DEPRESSURIZATION SYSTEM.  In basement or   	grade/crawl  space  foundations  shall  have  separate

   		slab-on-grade buildings, the following components of   	radon vent pipe shall terminate above the roof.

   		a passive sub-slab depressurization system shall be

   		installed during construction.

      											1303.11 POWER SOURCE.  To provide for future

   		1303.6.1 VENT PIPE.  A minimum 3-inch diameter   	installation of an active sub-membrane or sub-slab

   		(76 mm) ABS, PVC or equivalent gas-tight pipe shall   	depressurization   system,    an   electrical   circuit

   		be used to ensure that the pipe opening remains within   	terminated in an approved box shall be installed during

   		the sub-slab permeable material.  Alternatively, the 3-   	construction in the attic or other anticipated location of

   		inch (76mm) pipe shall be inserted directly into an   	vent pipe fans.   An electrical supply shall also be

   		interior perimeter drain tile loop or through a sealed   	accessible in anticipated locations of system failure

   		sump cover where the sump is exposed to the sub-slab   	alarms.

   		aggregate  or  connected  to  it  through  a  drainage

   		system.

   		The pipe shall be extended up through the building

   		floors,terminate at least 12 inches(305 mm)above the

   		surface of the roof in a location at least 10 feet (3048

   		mm) away from any window or other opening into the

   		conditioned spaces of the building that is less than 2

   		feet (610 mm) below the exhaust point, and 10 feet

   		(3048 mm) from any window or other exhaust point

   		and 10 feet (3048 mm) from any window or other

   		opening in adjoining or adjacent buildings.

   		1303.6.2 MULTIPLE PIPE VENTS.  In buildings

   		where interior footings or other barriers separate the

   		sub-slab aggregate or other gas-permeable material,

   		each area shall be fitted with an individual vent pipe.

   		Vent  pipes  shall  connect  to  a  single  vent  that

   		terminates separately above the roof.\

   		1303.7 VENT PIPE DRAINAGE.  All components

   		of the radon vent pipe system shall be installed to

   		provide positive drainage to the ground beneath the

   		slab or soil-gas-retarder.