Wyoming Digital Archives

 
��ORDINANCE NO. _535���� ��ui��oih?ll."Jc,/e��r"r,V/_ 

AN ORDINANCE PROVIDING FOR THE LICENSING OF PLUMBERS1 PERMITS, 

INSPECTIONS, GENERAL REGULATIONS COP?CERTTING QUALITY A'11) WEIGHT OF MATERIALS, 

NND GENERAL REGULATIONS COTSCERNING THE: INSTALLATION OF FIXTURES, DRAINS, ETC. 

0 IT ORDAINED BY THE TOWN COUNCIL OF THE TOWN OF THE'CITY OF SUNDANCE. 

Section 1. Definitions. The purpose of this Ordinance and certain 

words and phrases herein are defined as follows: 

(a) Building: an architectural structure covered by one roof having 

closed walls with doors and windows therein. 

(b) Private dwelling: a dwelling house detached from any other build- 

ing, designed for the use of one family only, and having not to exceed one 

kitchen and one meter for measuring electric current. 

(c) Rural and isolated residences: those situated at such distance 

from a public sewer system that their drainage cannot become tributary 

thereto. 

(d) Plumbing system: The water distribution pipes, fixtures, and 

fixture traps, soil, waste, and vent pipes, house drain and house sewer and 

storm water drainage, with their appurtenances and cinnection s, all within 

or adjoining to the building; 

(e) Plumbing fixtures: receptacles intended to receive and discharge 

water, liquid, or water -carried waste, into a drainage system with which 

they are connected. 

(f) Sanitary plumbing: plumbing that is free from defects in con- 

struction, conforms in every particular to the provisions of this Ordihance, 

and.is so designed and installed that it can be kept clean. 

'(g) Water service pipes: the pipe.from the water main to the build- 

"  g served. 

(h) Storm water drain: any pipe" or drain which receives any discharge 

of rain water from buildings or premises; or any seepage or ground water, 

and conveys the same to any public sewer, building sewer or water course. 

(1) Water distribution pipes: those which convey water from the 

service pipe to the plumbing fixture. 

(j) Vent pipe: any pipe provided to ventilate a building drainage 

system and " ..to." prevbnt,.trdp siphonage and'. -back pressure. 

(k) Continuous vent: a pipe extending vertically above the soil or 

waste branch. 

(1) Circuit vent: a pipe which vents a series of fixture traps on 

the same soil or water branch, and which is continued through the roof or 

reconnected into a vent stack above all fixture trap branches. 

(m) Unit vent: 'a pipe so arranged that it will vent two traps. 

(n) Return vent: an inverted emergency vent extended above the water 

line of the fixture and returned to a point of connection with the horiz- 

ontal run of the waste pipe from the fixture served on the sewer side of 

the branch waste from the fixture. 

(o) Waste vent: That part of a stack which extends above the 

highest installed fixture trap other than a water closet. 

(p) Soil vent: a part of a stack which extends above the highest 

installed water closet. 

(q) Stack vent: a pipe connecting to the side inlet of a fitting 

venting a water closet. 

(r) Wet vent: a pipe used to vent a trap which is also used as a 

" ste pipe from another trap. 

(s) Revent (or backvent): that part of a vent pipeline which 

connects directly with an individual trap, underneath or back of the 

fixture p and extends either to the main or branch ve��it pipe. 

(t) Local vent: a pipe through which foul air is removed from a 

room or the house side of a fixture. 

(u) Sewage: any liquid waste containing animal or vegetable waste 

in suspension or solution; may include liquids from laboratories or 

industrial institutions containing minerals in solution, 

(v) House sewer: that part of the horizontal piping of a drainage 

system extending from the house drain to its connection with the main 

sewer, sewage treatment tank, or leaching well. 

(w) Sanitary sewer: a drain or sewer constructed to convey organic 

Obwage from buildings in a septic tank or bacterial treatment tank or 

other point of disposal, and from which all surface and storm water is 

excluded. 

(x) Septic or sewage treatment tank: a water-tight receptacle so 

constructed as to promote the separation and decomposition of raw sewage 

which, by bacterial action and sedimentation, effects a process of clar- 

ification but does not purify the effluent. 

(y) Leaching well or cesspool: any pit or receptacle having porous 

walls which permit seepage into the ground. 

(z) Trap: a fitting or device so constructed as to prevent the pass- 

age of air or gas through it without materially affecting the flow of 

sewage or waste water through it. 

(aa) Trap seal: the vertical distance between the crown weir and 

the depth of the trap. 

(bb) The Durham System: the Durham System of plumbing is an 

installation of waste and soil pipes constructed of brass, copper, 

wrought iron, steel or cast iron pipes joined together'by means of 

threaded drainage fittings. 

(cc) Lead and Spil System: a lead and soil system of pluinbing 

is an installation of soil and waste pipes constructed of lead and cast 

iron soil pipes joined together by means of wiped and caulked joints. 

(dd) Subsoil drain: that part of a drainage system which conveys 

the subsoil, ground or seepage water from the foot walls or from below 

the cellar bottom under buildings to the building drain, storm water "  

drain, or building sewer. 

(ee) Waste pipe: any pipe which receives the discharge of any 

fixture, except water closets, and conveys the same to the house drain, 

soil or waste stacks. When such a pipe does not connect directly with 

a house drain or soil stack, it is termed a special waste. 

(ff) Soil pipe: any pipe which conveys the discharge of water 

closets with-or without the discharge from other fixtures. 

(gg) House drain: 'any system of horizontal, vertical, or continuous 

piping which receives the wastes from fixtures, outlets, or traps, directly 

or through branch pipes. 

(bb) Branch: the branch of any system of piping is the part of the 

system which extends horizontally at a slight grade, with or without 

lateral or vertical extensions or vebtical arms, from the house drain.to 

receive fixture outlets not directly connected to the house drain. 

(ii) Stack: a general term for any vertical line of soil, waste, 

or ve`tjpiping. 

j) Conductor: 'pipe which carries the storm or rain water from 

the roof of a building to the building sewer or storm water drain. Down 

spout is the term which is frequently used to denote the vertical portion 

of a conductor or roof ladder. 

(kk) Dead end: a branch leading from a soil, vent, waste, building 

sewer, which is terminated at a developed distance of two feet or more by 

means of a cap, plug, or other fitting not used for admitting water to the 

pipe. 

(11) Size and length: the given calibre of size of a pipe is Por "  

a nominal internal diameter. The developed length of a pipe is its 

-length along the center line of pipe and fittings. 

(mm) .Wiping a joint: a method of joining together two pieces of 

metal, to which solder is applied on the joint to a uniform heat suff- 

icient to obtain a smooth, neatly wiped finish, and having a thickness of 

solder not less than one fourth inch over the part of the joint where the 

metal joins. 

Section 2. Permit Required. With the exception of repairing leaks, 

cocks, or valves, or cleaning waste or sewer pipes, no person, firm or 

corporation, or owner shall construct, install, alter or remodel any 

plumbing or drainage, on or for any building in the Town, without securing 

��in advance, from the Building Inspector, a permit therefore. 

Section 3. Permit And Re -ins action Pees. There shall be no charge 

by the Building Inspec or for permits covering the installation of any 

plumbing, the laying of any drain or the tapping of a sewer or water line; 

and there shall be no charge made for any reinspection necessary. 

Section 4. Inspection. 

(a) All plumbing and steam fitting installation and connections 

therewith shall be subject to inspection by the Building Inspector, who 

shall ascertain any and all. violations of this Ordinance. 

(b) The equipment, material and labor necessary for inspection and 

test shall be furnished by the permittee. 

(c) All work installed shall be tested in the rough, with a water 

And air test, and all joints shall be made tight. In cases where inspec- 

tion in the rough is not feasible within eight working hours after request 

for inspection is received, the Building Inspector shall notify the 

plumber to proceed with the work. If, upon inspection the character of 

the work is such as to cause a reasonable doubt as to its tightness, 

it shall be subject to a test upon the direction of the Building Inspector. 

(d) If inspection or test bf plumbing reveals improper installation 

or defects in material, such defective material or imporper installation 

shall be replaced, altered or repaired not later than a date specified in 

writing on a tag,or label attached to the system, in a conspicuous,blace 

by the Building Inspector. 

(e) Upon the satisfactory completion and final inspection of the 

plumbing, a tag or label of approval shall be attached to the sy.stem71i1- 

a conspicuous place, certifying that the plumbing has met the require- 

ments of the Building Inspector. r 

(f) No permit or test shall be required for the repair of an old 

fixture after forcing out stoppage or repairing a leak. 

Section 5. Separate Ditches for Service Pines. No water or other 

service pipe shall be placed in the same ditch with a gas service pipe, 

unless such water or other service pipe be placed not less than twelve 

inches horizontally from the gas pipe. 

Section 6. General Reeulations. 

(a) All horizontal sewer piping shall be run at a uniform grade of 

not less than one-eighth of an inch per foot, and shall be supported or 

anchored at intervals of not to exceed ten feet. All stacks shall be 

supported at their base and all pipes shall be rigidly 'secured. A11 

water pipes must run at a grade sufficient to assure complete drainage. 

(b) All changes in direction shall be made by the appropriate use 

of forty-five degree wyes, half wyes, long sweep quarter -bends, sixth, 

eighth, or sixteenth bends sanitary tees side opening sanitary tees 

and quarter bends. A sanitary cross shali be used on vertical stacks 

not less than four inches in diameter for floor outlet fixtures only. 

Other double and/or combination fittings of approved design only shall 

ae used. Short quarter bends may be used only when one fixture is 

ttached except after approval of the Inspector and in lieu of closet 

bends, by means of lead or soil studs. Tees, crosses, and quarter bends 

may be used in vent pipes. 